Process Control Troubleshooting 1 (C-274) Exam Prep
Free practice questions

Free C-274 Practice Questions

10 exam-style questions with answers and explanations, straight from our 1,030-question bank. Tap an answer to check yourself. When you're ready, take the scored version in the free practice test.

Start the free practice test → ★★★★★4.9/5 from 2,400+ candidates · No signup

These 10 free C-274 questions are organized by exam domain, so you can see how each part of the Process Control Troubleshooting 1 (C-274) blueprint is tested. Reveal the answer and explanation under each question.

Domain 1: apply process control troubleshooting safety procedures

Question 1

Before opening a transmitter's process connection, a technician locks out the identified pressure source and releases trapped liquid through the designated drain. The gauge reaches zero. After the drain is closed, pressure begins to build again; no process fitting has yet been loosened. Under the hazardous-energy procedure, what must happen before the connection is opened?

Show answer & explanation

Correct answer: D - Identify and control the source of renewed pressure, then verify isolation remains effective before opening.

Domain 2: troubleshoot pressure-type liquid level sensors

Question 2

After a series-connected indicator is added, a two-wire level transmitter reads correctly near the bottom of its range but cannot deliver the required high-end current. The supply holds at 24 V DC, and the transmitter requires at least 12 V at its terminals. The receiver, new indicator, and wiring contribute 250 ohms each; there are no other voltage drops. At the required 20 mA, which voltage-budget assessment is correct?

Show answer & explanation

Correct answer: C - 9 V would remain; excessive loading leaves insufficient transmitter voltage.

Domain 3: troubleshoot analog flow sensors

Question 3

During verification of an orifice flow-measurement loop, the specified 4-20 mA output must be linear in flow over 0-200 L/min. At a reference flow of 120 L/min, the transmitter indicates 120 L/min and delivers 13.6 mA to the receiver, but the receiver displays 154.9 L/min. Both instruments agree at zero and full-scale flow. Which correction addresses the midrange mismatch without disturbing those endpoints?

Show answer & explanation

Correct answer: C - Remove the extra square-root extraction at the receiving instrument.

Question 4

An electromagnetic meter on a conductive rinse-water line becomes erratic after the piping is rerouted over a high point. Independent flow remains steady. An inspection confirms that an air pocket leaves the meter's tube partly empty, while grounding and analog-signal checks pass. Which intervention addresses the measurement fault rather than concealing its symptoms?

Show answer & explanation

Correct answer: C - Restore a fully liquid-filled measuring tube and repeat the flow check.

Domain 4: troubleshoot pneumatic proportional valves and I/P converters

Question 5

A flow loop repeatedly overshoots its setpoint. A synchronized trend shows the controller current and pressure at the actuator changing smoothly, but the actual valve stem remains stationary and then jumps. The same stick-and-jump motion occurs in both travel directions. Instrument-air pressure remains adequate throughout. Which fault best explains this pattern?

Show answer & explanation

Correct answer: B - Excessive static friction in the valve assembly

Question 6

With the process isolated for a full-stroke test, a direct-acting I/P specified for 4-20 mA to 3-15 psig produces 3 psig at 4 mA and 9 psig at 12 mA, but only 10.5 psig at 20 mA. Actual input current is verified. The installation calls for a 20 psig air supply: the header remains at 20 psig, but pressure at the I/P supply port falls to 11 psig during the upper-end test. The appropriate first correction is to:

Show answer & explanation

Correct answer: A - Restore the specified air supply at the I/P under demand.

Domain 5: troubleshoot loop controllers

Question 7

Commissioning checks confirm that increasing controller current raises I/P pressure and closes an air-to-close tank inlet valve. In automatic operation, however, a rise in measured level above setpoint causes current to fall, opening the inlet farther and accelerating the level rise. The measurement is accurate. Which controller change corrects the feedback direction while retaining the specified valve and I/P arrangement?

Show answer & explanation

Correct answer: A - Change control action so output current increases when measured level rises.

Domain 6: identify systems-level process control troubleshooting methods

Question 8

A level indication has stopped responding to actual tank changes. With the process secured for testing, the technician disconnects the transmitter at its field terminals and connects a loop calibrator in simulate mode using the existing loop supply. The receiver correctly displays the configured low, middle, and high values when 4, 12, and 20 mA are simulated. What has this test actually demonstrated?

Show answer & explanation

Correct answer: D - The wiring and receiver pass these signal checks; pressure sensing is still untested.

Domain 7: troubleshoot a closed-loop liquid level control system

Question 9

A recipe change replaces a liquid of density 1,000 kg/m³ with one of density 800 kg/m³. A vented tank's hydrostatic transmitter still converts pressure to level using 1,000 kg/m³. Its pressure measurement is accurate, there is no mounting offset, and the liquid has uniform density. Automatic inlet control settles at an indicated setpoint of 1.20 m. The maximum permitted actual level is 1.40 m. How should the apparent zero control error be interpreted?

Show answer & explanation

Correct answer: B - Actual level is 1.50 m; the indicated setpoint conceals an inventory above the operating limit.

Domain 9: troubleshoot an on/off liquid level control system

Question 10

An operator reports that a fill pump has failed because it is off while the tank is below the upper level setting. The two-point control starts filling at 30% and stops at 70%. The pump stopped at 70%, and normal withdrawal has since lowered the level to 50%. All permissives are healthy, and the level is within the permitted operating band. What response is warranted?

Show answer & explanation

Correct answer: A - Leave automatic control active; the next start is due at 30%.

The rest of the C-274 blueprint

The C-274 exam also covers these domains. Drill them in the full free practice test:

That's 10 of 1,030

The full bank has 1,020 more C-274 questions with explanations.

Continue in the free practice test →

View plans